4. Application to a Case Study: Fire Safety in Historical Theaters

verfasst von : Gabriele Bernardini

Erschienen in: Fire Safety of Historical Buildings

Verlag: Springer International Publishing

Aktivieren Sie unsere intelligente Suche, um passende Fachinhalte oder Patente zu finden.

search-config
loading …

Abstract

Historical theaters represent a representative case-study in Building Heritage fire-safety issue, because of environmental factors (e.g.: structures vulnerability, fire source presence, artistic value of building, building layout) and occupants’ features. (mainly: high occupants density, level of familiarity with architectural spaces). This chapter compares different solutions to the wayfinding issue in similar scenarios, by means of an Italian significant case-study. Experimental drills and simulation activities are used in order to define the effectiveness of innovative wayfinding systems (both “active” and “passive”) in comparison to the current evacuation facilities. Results show how the proposed systems enhance motion speeds, evacuation times, and the percentage of people choosing the correct evacuation paths because they are effectively able to supply people needs in evacuation and interact with their behaviours. At the same time, solutions involve easy-to-apply building components, that are introduce no architectural modifications to the original building layout and features.

Sie haben noch keine Lizenz? Dann Informieren Sie sich jetzt über unsere Produkte:

Springer Professional "Wirtschaft+Technik"

Online-Abonnement

Mit Springer Professional "Wirtschaft+Technik" erhalten Sie Zugriff auf:

  • über 102.000 Bücher
  • über 537 Zeitschriften

aus folgenden Fachgebieten:

  • Automobil + Motoren
  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Elektrotechnik + Elektronik
  • Energie + Nachhaltigkeit
  • Finance + Banking
  • Management + Führung
  • Marketing + Vertrieb
  • Maschinenbau + Werkstoffe
  • Versicherung + Risiko

Jetzt Wissensvorsprung sichern!

Springer Professional "Technik"

Online-Abonnement

Mit Springer Professional "Technik" erhalten Sie Zugriff auf:

  • über 67.000 Bücher
  • über 390 Zeitschriften

aus folgenden Fachgebieten:

  • Automobil + Motoren
  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Elektrotechnik + Elektronik
  • Energie + Nachhaltigkeit
  • Maschinenbau + Werkstoffe




 

Jetzt Wissensvorsprung sichern!

Springer Professional "Wirtschaft"

Online-Abonnement

Mit Springer Professional "Wirtschaft" erhalten Sie Zugriff auf:

  • über 67.000 Bücher
  • über 340 Zeitschriften

aus folgenden Fachgebieten:

  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Finance + Banking
  • Management + Führung
  • Marketing + Vertrieb
  • Versicherung + Risiko




Jetzt Wissensvorsprung sichern!

Fußnoten
1
Some examples of famous theaters that burned to the ground is offered here http://​www.​telegraph.​co.​uk/​culture/​theatre/​theatre-features/​10099440/​Ten-theatres-that-burned-to-the-ground.​html. Accessed 19 Sept 2016.
 
2
From this point of view, it becomes essential the simulation of fire spreading by using, for example, fire dynamics simulators.
 
3
As for other space in which audiences seat in rows [10], a person, who delays his/her evacuation start inside the row, could completely block the way for other people to evacuate, because of the small width between two row seats suggested by fire-safety codes (e.g.: in Italy, 80 cm [7]).
 
4
Such as for other historical environments, the fire suppression system should use adequate fire extinguishers in relation to the type of fire (e.g. according to the EN2), the presence of people during or after the fire suppression, the preservation of not burned elements after the emergency.
 
5
These exits are often connected to recent interventions due to prescriptive fire-safety codes [2, 7].
 
6
In fact, being less than 1000 individuals, no firebreak curtains are needed for current Italian regulations.
 
7
This means that occupants’ densities along evacuation paths is ideally lower than 0.54 pp/m2 and so no group motion effects are taken into account.
 
8
For their dimensions, stairs are generally approximated to the dimensional category to 165–305 mm.
 
9
According to Sect. 3.​2 description.
 
10
Added during the experiments.
 
11
DIN 67510 - Photoluminescent pigments and products; ISO 16069:2004 - Graphical symbols - Safety signs - Safety way guidance systems (SWGS) - annex B.
 
12
According to Table 4.2, about 170 individuals uses each of the two main staircases (down to 1st): these evacuees need about 120 s to pass through the staircase. The most distant occupants also need 60 s to reach 5I (horizontal motion), move along the last stairs flight and then reach ME (horizontal motion again).
 
13
Data from: Italian Institute of Statistics (ISTAT) (2015) Italia in cifre. http://​www.​istat.​it/​it/​files/​2015/​08/​ItaliaInCifre201​5It.​pdf. Accessed 5 Nov 2016.
 
14
In particular, people declared to have normal or corrected-to-normal vision.
 
15
By using an eye-patch with a mean 16% visible ray degree of transmissivity, that corresponds to 3–7 m visibility distance (smoke density of about 0.26–0.60 m\(^{-1}\)). Environmental illuminance at the ground in accordance with UNI EN 1838:2000: for corridor, 5 lux (>2 lux): for stairs, 15 lux (>5 lux).
 
16
An average illuminance of 0.5 lux on stair-steps were provided so as to reduce experimental risks for participants.
 
17
On staircases.
 
18
For staircases, refer to Case 3-rounded signs with installation gap of 90 cm for minimum value (0.67 m/s) and Case 4-strips at each stair step for maximum value (0.7 m/s) in the speed range (these values are average data from the whole number of individual’s drills). For corridors, refer to Case 3, B3F, L-shaped testing scenario.
 
19
From either SS and BC conditions.
 
20
In general terms, people sharing family ties seated nearby.
 
21
According to Eq. 3.​2.
 
22
According to the emergency plan.
 
23
Egress time started at the alarm sound.
 
24
Since initial occupants’ densities are really close to the free-flow ones.
 
25
By supposing that: the number of exited pedestrians is the experimental one; all people start moving at the same time, so as to obtain conservative density-speed correlations along the motion path.
 
26
BO has lower speeds in respect to SS.
 
28
Compare with Sect. 2.​4.​2.
 
29
The value associated to the parterre is chosen in a conservative way.
 
30
Times approximation to the next 5 s, as for the other used RSET evaluation methods [27].
 
31
According to Eq. 3.​2 and Sect. 4.2.2 similar KPIs, the referring conditions is represented by scenario 0.
 
Literatur
5.
Zurück zum Zitat Bernardini G, Azzolini M, D-Orazio M, et al (2016) Intelligent evacuation guidance systems for improving fire safety of Italian-style historical theatres without altering their architectural characteristics. J Cult Herit. doi:10.1016/j.culher.2016.06.008 Bernardini G, Azzolini M, D-Orazio M, et al (2016) Intelligent evacuation guidance systems for improving fire safety of Italian-style historical theatres without altering their architectural characteristics. J Cult Herit. doi:10.​1016/​j.​culher.​2016.​06.​008
11.
Zurück zum Zitat Lena K, Kristin A, Staffan B et al (2010) How do people with disabilities consider fire safety and evacuation possibilities in historical buildings-a Swedish case study. Fire Technol 48:27–41. doi:10.1007/s10694-010-0199-0 CrossRef Lena K, Kristin A, Staffan B et al (2010) How do people with disabilities consider fire safety and evacuation possibilities in historical buildings-a Swedish case study. Fire Technol 48:27–41. doi:10.​1007/​s10694-010-0199-0 CrossRef
15.
Zurück zum Zitat Babrauskas V, Fleming JM, Russell BD (2010) RSET/ASET, a flawed concept for fire safety assessment. Fire Mater 34:341–355. doi:10.1002/fam CrossRef Babrauskas V, Fleming JM, Russell BD (2010) RSET/ASET, a flawed concept for fire safety assessment. Fire Mater 34:341–355. doi:10.​1002/​fam CrossRef
16.
Zurück zum Zitat Quagliarini E (2008) Wooden structures in Italian style theatres between the 18 and 19 century (in Italian). Firenze, Italy Quagliarini E (2008) Wooden structures in Italian style theatres between the 18 and 19 century (in Italian). Firenze, Italy
17.
Zurück zum Zitat D’Ettorre A, Montemurro E (1996) The “white” book: historic theaters in the Marche: state of art of restoration and financial requirements (Libro bianco: I teatri storici nelle Marche: lo stato del recupero ed il fabbisogno finanziario) (in Italian). Lithos, Ancona D’Ettorre A, Montemurro E (1996) The “white” book: historic theaters in the Marche: state of art of restoration and financial requirements (Libro bianco: I teatri storici nelle Marche: lo stato del recupero ed il fabbisogno finanziario) (in Italian). Lithos, Ancona
18.
Zurück zum Zitat D’Orazio M, Bernardini G, Tacconi S et al (2016) Fire safety in Italian-style historical theatres: how photoluminescent wayfinding can improve occupants- evacuation with no architecture modifications. J Cult Herit 19:492–501. doi:10.1016/j.culher.2015.12.002 CrossRef D’Orazio M, Bernardini G, Tacconi S et al (2016) Fire safety in Italian-style historical theatres: how photoluminescent wayfinding can improve occupants- evacuation with no architecture modifications. J Cult Herit 19:492–501. doi:10.​1016/​j.​culher.​2015.​12.​002 CrossRef
22.
Zurück zum Zitat Italian Organization for Standardization (UNI) (2004) UNI 7543:2004 - Safety colours and safety signs Italian Organization for Standardization (UNI) (2004) UNI 7543:2004 - Safety colours and safety signs
24.
Zurück zum Zitat Bernardini G, Quagliarini E, D’Orazio M, Santarelli S (2016) How to help elderly in indoor evacuation wayfinding: design and test of a not-invasive solution for reducing fire egress time in building heritage scenarios. In: Foritaal (2016) (in press) Bernardini G, Quagliarini E, D’Orazio M, Santarelli S (2016) How to help elderly in indoor evacuation wayfinding: design and test of a not-invasive solution for reducing fire egress time in building heritage scenarios. In: Foritaal (2016) (in press)
27.
Zurück zum Zitat Nelson HE, Mowrer FW (2002) Emergency movement. In: SFPE handbook of fire protection engineering. National Fire Protection Association, pp 367–380 Nelson HE, Mowrer FW (2002) Emergency movement. In: SFPE handbook of fire protection engineering. National Fire Protection Association, pp 367–380
32.
Zurück zum Zitat Pu S, Zlantanova S (2005) Evacuation route calculation of inner buildings. In: Research book chapter in geo-information for diaster management, Springer. pp 1143–1161 Pu S, Zlantanova S (2005) Evacuation route calculation of inner buildings. In: Research book chapter in geo-information for diaster management, Springer. pp 1143–1161
Metadaten
Titel
Application to a Case Study: Fire Safety in Historical Theaters
verfasst von
Gabriele Bernardini
Copyright-Jahr
2017
DOI
https://doi.org/10.1007/978-3-319-55744-1_4