Alternatives to Enhance Flat Slab Ductility

Authors: Mohamed Husain, Ahmed S. Eisa, Ramy Roshdy

Published in: International Journal of Concrete Structures and Materials | Issue 1/2017

Activate our intelligent search to find suitable subject content or patents.

search-config
loading …

Abstract

Flat slab systems are vastly used in multi-story buildings because of their savings in story height and construction time, as well as for their flexibility in architectural remodeling. However, they frequently suffer brittle punching-shear failure around columns, especially when subjected to lateral loads. Therefore, seismic codes labeled flat slabs as non-ductile systems. This research goal is investigating some construction alternatives to enhance flat slab ductility and deformability. The alternatives are: adding different types of punching-shear reinforcement, using discreet fibers in concrete mixes, and increasing thickness of slab around columns. The experimental study included preparation and testing of seven half-scale interior slab-column connections up to failure. The first specimen is considered a reference, the second two specimens made of concrete mixes with different volumetric ratios of polymer fibers. Another three specimens reinforced with different types of punching-shear reinforcement, and the last specimen constructed with drop panel of inverted pyramidal shape. It is found that using the inverted pyramid-shape drop panel of specimen, increases the punching-shear capacity, and the initial and the post-cracking stiffnesses. The initial elastic stiffnesses are different for all specimens especially for the slab with closed stirrups where it is experienced the highest initial stiffness compared to the reference slab.

1 Introduction

Flat slabs are preferred in multi-story construction due to its economical and architectural benefits. These benefits include; reducing the construction time and reducing story height, which results in more stories for the same building, as well as their flexibility in architectural remodeling. However, they have been discredited by many seismic codes for less ductile behavior, and poor energy absorption (IBC 2009; Eurocode 8 2004; ACI 421-1R 2008).
The capacity design method has been widely adopted by a majority of modern seismic codes, since its introduction in the New Zealand code in mid-1970s (Park and Paulay 1974; Paulay and Priestley 1992; Dovich and Wight 1996; Robertson and Johnson 2004). The method uses ductility and energy absorption characteristics of structures to dissipate large amount of the seismic imparted energy, which boosts the structural safety and reliability. It requires flexural yielding at many locations of the building and provides them with adequate ductility. At the same time prevent any possibility of brittle failure, such as, shear and bond failures.
Punching shear reinforcement is increasingly used in flat slabs because of the significant improvements introduced in strength and ductility as demonstrated in Fig. 1. Two identical slab models with and without punching-shear reinforcement were tested (Ruiz and Muttoni 2010). It was observed that the strength of slab with shear reinforcement has almost double the strength of the slab without shear reinforcement; also the deformation capacity is increased more than three times. The main objective of this research is to evaluate the potential of using different alternatives for enhancing the ductility and deformability of flat slab new construction.
Hawkins (1974), Dam and Wight (2015) and Matzke et al. (2015) published a paper presenting an overview of tests performed with different punching-shear reinforcement systems such as steel heads, bent-up bars, and stirrups. During the 1980s and 1990s, Regan started his research on punching with and without shear reinforcement at the Polytechnic of Central London (Regan 1981, 1985). In the UK at the beginning of the 1990s, Chana and Desai have performed extensive experimental investigations on punching-shear tests with shear reinforcement (Chana and Desai 1992). Oliveira et al. (2000) have carried out experimental punching investigations on the effects of vertical or inclined stirrups on flat slab behavior. Carvalho (2011) also have conducted investigations on the same subject.
Another way to increase shear strength is to add fiber to concrete as shear reinforcement. Dinh et al. (2010) have tested 28 simply supported beams with 3.5 shear span/depth ratio, with different fiber volumetric ratio. They concluded that fiber concrete with appropriate fiber volumetric ratio can provide shear reinforcement to concrete beams. Meisami et al. (2013) have investigated the shear strengthening of flat slab by using fibers-reinforced concrete. In the early 1990s, a team of researchers from University of California, at Berkeley, has assessed the seismic performance of 14-story-non ductile-reinforced concrete built in middle 1960s. The building was termed non-ductile, because it was designed on code provisions prior to the 1976 seismic code (Graf and Mehrain 1992). The building has survived two major seismic events—San Fernando Valley in 1971, and Loma Prieta 1989—only by slab column framing action. It is concluded that the building exceptional behavior has to do with its inverted pyramid-shaped drop-panels. The ductility of flat plates: comparison of shear reinforcement systems have been studied (Broms 2007).

2 Experimental Program

Experimental studies were designed to achieve the objectives of this research. The experimental study included construction and testing of seven half-scale interior slab-column connections reinforced with the same steel bars in two direction top and bottom. The first specimen is considered a reference, the second two specimens made of concrete mixes with different volumetric ratios of polymer fibers. Another three specimens reinforced with different types of punching-shear reinforcement, and the last specimen constructed with drop panel of inverted pyramidal shape. Each specimen had a square plan of side length dimension of 1500 mm and a central column stub of cross section (200 mm × 200 mm) extending 600 mm beyond the top surface of the slabs. The test specimens were supported along all four edges. A concentric load was applied to the slabs through the column stub. Through the experimental program, the effects of the following parameters were investigated: (i) type of additional punching shear reinforcement; (ii) concrete with polymer fiber; (iii) slab thicknesses of 120 and 180 mm by adding pyramidal drop panel. All slabs were designed based on the ACI-421.IR two-way slab systems.
The slab-column connection specimens are built and tested under gravity load, and the specimens are inclined with an angle of 20° that give vertical and horizontal loads on the specimens as shown in Fig. 2. The vertical load represents gravity (dead and live) loads and the horizontal load represents an equivalent static lateral load on the slab. Figure 3 shows the specimen testing setup. All slabs were reinforced with steel bars in two orthogonal directions top and bottom. Each specimen is square in plan with side-length dimension of 1500 mm, and a central column stub extending 600 mm above the top surface of the slabs. The test specimens were simply supported along all four edges. A concentric load was applied to the slabs through the column stub from the top side. Through the experimental program, the effects of the following parameters were investigated: (i) type of additional punching shear reinforcing; (ii) polymer fiber; (iii) slab thickness. Table 1 summarize the details of the tested specimens.
Table 1
Characteristics and dimensions of the specimens.
Specimen
S1
S2
S3
S4
S5
S6
S7
Effect
Control
Fiber 0.2%
Fiber 0.3%
Stud-rails
Multi-leg stirrups
Closed stirrups
Drop panel
Thickness (mm)
120
120
120
120
120
120
180
Effective depth (mm)
95
95
95
95
95
95
155
Top reinforcement spacing (mm)
200
Bottom reinforcement spacing (mm)
167
Steel studs spacing (mm)
N/A
N/A
N/A
60
N/A
N/A
N/A
Closed stirrups spacing (mm)
N/A
N/A
N/A
N/A
N/A
60
N/A
Steel studs have a head diameter of 300 mm, shear stud’s shaft diameter of 100 mm, the steel base rail has a thickness of 60 mm with a length of 400 mm and the thickness of 10 mm whereas the total height is 106 mm. The shear studs have a yield strength of 360 N/mm2. The multiple-leg stirrups arranged every 60 mm, and the height of the stirrup is 100 mm and the diameter is 6 mm. The closed stirrups used in slab S6, arranged every 60 mm with a diameter of 6 mm. All slabs have 5ϕ8/m as a top reinforcement and 6ϕ12/m as a bottom reinforcement. The shear studs and stirrups are arranged at a distance of 0.5 d from the column face.

2.1 Material Properties

All concrete mixtures were normal weight concrete and tested for a 28-day’s compressive strength with an average of (310 kg/cm2). Coarse aggregate in the concrete mixture consisted of crushed basalt rock from Ataqa area in Egypt, the mix proportions of concrete for 1.0 m3 of concrete is shown in Table 2. Polymer fiber concrete used for specimens S2 and S3 with different ratio are shown in Table 2.
Table 2
Concrete mix proportions of 1.0 m3.
Ingredient
Cement (kg)
Fine aggregate (m3)
Coarse aggregate (m3)
Water (kg)
 
350
0.4
0.8
250
Different ratio of polymer fiber on specimen S2 and S3
 
Cement (kg)
Cement per specimen (kg)
Fiber per specimen
S2
350
103
0.2% = 206 g
S3
350
103
0.3% = 309 g
The characteristic yield strength of steel bars was 360 MPa and the mean yield strength of the steel bars was f y  = 382 MPa (obtained from direct tension tests on three specimens). The ultimate strength of the steel bars was f u  = 532 MPa and the average uniform elongation of bars at f u was ε u  = 11%.

2.2 Test Setup

A vertically oriented hydraulic actuator, connected to a steel reaction frame, is used for application of the load to the slab specimens that shown in Fig. 3. This setup helps to subject the connection to horizontal and vertical loads to create unbalanced moment typical of lateral loads.
The installation of strain gages for concrete structures presents several unique challenges to the installer, whether measurements are made on the concrete surface or within the concrete, or on reinforcement bars within the structure. Figures 4 and 5 show the location of stain gages installed in the present study. The deflection of the test specimens was captured with linear variable differential transformers (LVDT). Figure 6 shows the specimen details for all the tested slabs.

3 Results and Discussion

3.1 Load Deflection

The typical load-deflection behavior of all specimens was linear up to the yield load, when the yield of the longitudinal steel reinforcement was reached; the behavior changed to nonlinear up to failure. The cracking failure loads and corresponding vertical deflections for all tested specimens are listed in Table 3.
Table 3
Specimen’s cracking load, failure load, and deflection.
Specimens
Cracking load (kN)
Failure load (kN)
Deflection at failure (mm)
Failure mode
S1
20
130
13
Brittle
S2
22
135
15.5
Brittle
S3
23
141
17
Brittle
S4
25
200
22
Ductile
S5
27
220
28
Ductile
S6
30
244
35
Ductile
S7
35
300
N/A
Load-deflection curves of all specimens S1, S2, S3, S4, S5, S6 and S7, respectively are presented in Fig. 7 and Table 3. The control slab is failed at an ultimate load of 130 kN with a corresponding deflection of 13 mm. The addition of fiber to the concrete mixtures has a noticeable effect on the ultimate load, where the 0.2 and 0.3% of fiber increased the ultimate load by 3.8 and 8.4%, respectively. The ultimate deflection increased by 19.2 and 30.7% for the 0.2 and 0.3% fiber volume, and compared to the control deflection. Using steel studs around the slab-column connection enhanced the ultimate load and deflection significantly by 53.8 and 69.23%, respectively compared to the control specimen. A similar behavior was noticed when using the stirrup legs as well. An outperformed behavior was obtained when the slab-column connection was reinforced by closed stirrups, where the ultimate load and deflection increased by 87.7, and 269% respectively. Finally as it was expected, the pyramidal drop panel shape increased the ultimate load by 230% compared to the control specimens (Fig. 8).

3.2 Crack Pattern

The cracking load P cr and the mid-span deflection Δ corresponding to the cracking load of the specimens are given in Table 4. In regard to the P cr values reported in Table 4, it is concluded that the cracking load of the control slab without fibers, S1 is around 9–10% less than the cracking load of the slabs with fibers. This can be attributed partly to shrinkage induced cracks in the non-symmetrically reinforced sections; however, the uniform distribution of fibers in slabs S2 and S3 can lessen the shrinkage induced cracks.
Table 4
Load deflection at different load stages and shear strength.
Slabs
Pcr (kN)
Δcr (mm)
Py (kN)
Δy (mm)
Pu (kN)
Δu (mm)
Vu (measured shear strength) ACI 421-1R (N/mm2)
Vn (nominal shear strength) ACI 421-1R (N/mm2)
S1
20
0.5
112
10.5
130
13
3.00
1.83
S2
22
0.5
120
7.5
135
15.5
N/A
N/A
S3
23
0.6
120
8
141
17
N/A
N/A
S4
25
0.7
138
7.2
200
22
3.69
4.16
S5
27
0.6
140
6.4
220
28
5.08
1.1
S6
30
0.6
145
9
244
35
5.63
1.57
S7
35
0.8
185
14.5
300
2.97
1.83
The initiation and development of first cracking at mid-point of the control slab and the slabs with fibers of 0.2 and 0.3% by volume (S2 and S3) took place at deflection Δ cr of 0.5–0.6 mm, respectively (Table 4). The development of cracks at mid-span is associated with a small reduction in the load and a load drop followed the onset of first cracking is a characteristic of reinforced concrete members tested. The cracking load increased with the addition of the studs, stirrup legs and the closed stirrups by 25, 35, and 50%, respectively compared to the control specimen. It was seen that the maximum cracking load recorded from all the specimens tested was related to the addition if the pyramidal drop panel shape, where the cracking load reached 35 kN by an increase equal 75% compared to the control slab with and enhancement of the cracking deflection of 60%. The crack patterns of specimens S1, S4, and S5 are shown in Fig. 9. Specimen S7 did not reach failure due to lab limitations (available load capacity = 300 kN).
For measured shear stress (at maximum applied load P u recorded during the tests). The shear stress for all concrete slabs was predicted by the shear equation provided by ACI 421.1R as in the following:
$$ v_{\text{u}} = \frac{{{{V}}_{{u}} }}{{A_{c} }} + \frac{{\gamma_{vx} M_{ux} y}}{{J_{c} }}. $$
(1)
V u is the factored shear force and M ux is the unbalanced moment, A c is the concrete area resisting shear, J c is the polar moment of inertia. Y is the location where the maximum shear stress is calculated. More details could be found in the ACI 421.1R.
While the nominal shear strength in slabs S1, and S7, where shear reinforcement is not provided, were taken the smallest value of Eqs. 4–7b, 4–8b, and 4–9b in ACI421.1R. The shear strength of slabs with stirrups (S5 and S6) is calculated based on Eq. 4–11 in ACI 421.1R, and finally the nominal shear strength of slab S4 is calculated based on Sec. 4.3.3 in the same document.

3.2.1 Example Slab S4 (Shear Studs Provided)

$$ v_{u} \;({\text{Eq}}.1) =_{ } \frac{200{,}000\cos 20}{{2\left( {295 \times 95} \right) + 2(295 + 95)}} + \frac{0.4 \times 200{,}000\sin 20 \times 600 \times 295/2}{{\frac{{95^{3} \times 295}}{6} + \frac{{295^{3} \times 95}}{6} + \frac{{295 \times 295^{2} \times 95}}{2}}} = 4. 6 1 {\text{ N}}/{\text{mm}}^{ 2} $$
Column dimensions (c) = 200 × 200 mm2.
The critical section perimeter = c + d = 200 + 95 = 295 mm.
Column height = 600 mm.
P u  = 200,000 N.
The nominal shear strength is calculated based on the following:
$$ v_{c} = \frac{{\sqrt {f_{c}^{'} } }}{4} = 1.4\;{\text{N/mm}}^{2} $$
$$ v_{s} = \frac{{A_{v} }}{S} \times \frac{{f_{y } }}{{b_{0} }} = \frac{8 \times 78.5 \times 360}{60 \times (2 \times 295 + 2 \times 295)} = 2.79\;{\text{N/mm}}^{2} $$
$$ v_{n} = v_{c} + v_{s} = 1.4 + 2.79 = 4.16\;{\text{N/mm}}^{2} . $$
In Table 4; P cr and Δ cr : load and deflection of the specimen at first crack, P y and Δ y : load and deflection of the specimen at yield point, P u and Δ u : load and deflection of the specimen at yield point at failure. The following equations are used to define the cracking and yield points from the steel strain readings.
$$ \varepsilon_{Concrete} = \varepsilon_{Steel} = \frac{\delta }{{E_{Steel} }} = \frac{{n \times f_{ctr} }}{{E_{Steel} }} $$
$$ \varepsilon_{Steel} = \frac{{10 \times 1.9\sqrt {320} }}{{2 \times 10^{6} }} = 150 \times 10^{ - 6} = 150\;\mu \varepsilon $$
$$ \varepsilon_{y} = \frac{{\delta_{y} }}{{E_{Steel} }} = \frac{3600}{{2 \times 10^{6} }} = 1800 \times 10^{ - 6} = 1800\;\mu \varepsilon $$
Table 4 shows the shear strength resisted by concrete for all the slabs except S2, and S3. The predicted values based on the ACI 421-1R (2008) and it is noticed that the percentages of actual/predicted shear strength are varied. The closest prediction was for slab S7 where the actual-to-predicted shear strength was 0.96 and the worst prediction was for slab S4 where the percentage of difference was 0.65.

3.3 Slabs Ductility

The ultimate load capacity, P u , and the deflection value at ultimate load level, Δ u , and the ductility ratio, μ Δ (measure of ductility) are listed in Table 5. Specimen S2 and S3 failed in a more ductile manner than specimen S1, suggesting that the fibers added to the concrete mixtures enhanced the ductility by an average of 66% relative to the control slab and thus provided ductility to the reinforced concrete slab column connections. In terms of ductility provided by the shear studs layout improved the ductility by a significant percentage (246%) compared to the control slab. Both the shear legs and the closed stirrups provided outperformance of ductility where it was observed to be 353, and 314% respectively.
Table 5
Ductility ratio of all specimens.
Slab
Δ y (mm)
Δ u (mm)
μ Δ  = Δ u y
S1
10.5
13
1.238
S2
7.5
15.5
2.067
S3
8
17
2.125
S4
7.2
22
3.056
S5
6.4
28
4.375
S6
9
35
3.888
S7
14.5
N/A
Figure 10 shows ultimate load and deflection of the specimens, it shows that S7 exhibit higher strength with no signs of near failure, compared with all specimens. Also the bar chart for the ductility for all specimens was observed that S5 and S6 exhibited higher ductility compared with S4 that because the large number of stirrup legs in S5, and confinement of concrete of the closed stirrups S6.

4 Energy Absorption Index (EAI)

Previous research on the performance of buildings during severe earthquakes indicated that energy dissipation plays a very important role in protecting buildings from collapse. The EAI is defined as the ratio of the total area under load-deflection curve to that under the elastic part only as calculated in Eq. 2 (Fig. 11):
$$ EAI = \frac{{A_{1} + A_{2} }}{{A_{1} }} $$
(2)
The EAI is calculated and listed in Table 6, it shows that specimens S5 has the highest energy absorption, about 7.5 times of the value of the control specimen S1. Specimens S4 and S6 exhibited energy absorption about 3.8, and 7 times of the value of S1.
Table 6
EAI and stiffness of all slab specimens.
Slab
A1
A2
A1 + A2
EAI
K i
K s
S1
5.88
3.25
9.13
1.55
40.0
10.7
S2
4.5
10.8
15.3
3.40
44.0
16.0
S3
4.8
12.69
17.49
3.64
38.3
15.0
S4
4.97
29.6
34.57
6.96
35.7
19.2
S5
4.48
47.52
52
11.61
45.0
21.9
S6
6.53
63.44
69.97
10.72
50.0
16.1
S7
13.41
NA
NA
NA
43.8
12.8

4.1 Slab Stiffness

Two different stiffnesses the initial stiffness K i , and the post secant stiffness K s were obtained from experimental data by using Eq. 3, and listed in Table 6 (Fig. 12).
$$ K_{i} = \frac{{P_{cr} }}{{\Delta_{cr} }}\quad {\text{and}}\quad K_{s} = \frac{{P_{y} }}{{\Delta_{y} }} $$
(3)
Table 6 shows the initial stiffness for all specimens. It is observed that all specimens have almost the same elastic stiffness except S5 (due to stirrups legs) and S7 (due to the larger depth).

5 Conclusions

From this study the following conclusions can be drawn:
1.
The addition of the pyramid-shaped drop panel in specimen (S7), has led to the increased strength, initial stiffness, and secant stiffness.
 
2.
The initial stiffness of specimens reinforced with stud-rail have increased by about 12.5% compared to the control slab.
 
3.
The secant stiffness for specimens made of fiber concrete S2, and S3 have increased by about 49.5 and 40% relative to the control specimens.
 
4.
In terms of ductility provided by the shear studs layout improved the ductility by a significant percentage (246%) compared to the control slab. Both the shear legs and the closed stirrups provided outperformance of ductility where it was observed to be 353, and 314% respectively.
 
5.
Specimens S5 has the highest energy absorption index (energy dissipation), about 7.5 times of the value of the control specimen S1. Specimens S4 and S6 exhibited energy absorption about 3.8, and 7 times of the value of S1.
 
6.
Finally, the following conclusions on ductility shall be emphasized: The use of fiber concrete has increased the post-crack stiffness only with no ductility, deformability, or energy dissipation enhancements.
 
7.
Good ductility enhancements obtained by using multi-leg and closed stirrups as punching-shear reinforcements, even better than the ductility of the famous stud-rail reinforcement.
 
Open AccessThis article is distributed under the terms of the Creative Commons Attribution 4.0 International License (http://​creativecommons.​org/​licenses/​by/​4.​0/​), which permits unrestricted use, distribution, and reproduction in any medium, provided you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license, and indicate if changes were made.
Literature
go back to reference ACI 421-1R. (2008). Guide to shear reinforcement for slabs. Farmington Hills, MI: American Concrete Institute. ACI 421-1R. (2008). Guide to shear reinforcement for slabs. Farmington Hills, MI: American Concrete Institute.
go back to reference Broms, C. E. (2007). Ductility of flat plates: Comparison of shear reinforcement systems. ACI Structural Journal, 104(6), 703. Broms, C. E. (2007). Ductility of flat plates: Comparison of shear reinforcement systems. ACI Structural Journal, 104(6), 703.
go back to reference Carvalho, G. (2011). Análise Sísmica de Edifícios de Betão Armado Estudo de Alternativas de Modelação Análise Não-Linear. Master’s thesis, Instituto Superior Técnico, Universidade Técnica de Lisboa, Portugal. Carvalho, G. (2011). Análise Sísmica de Edifícios de Betão Armado Estudo de Alternativas de Modelação Análise Não-Linear. Master’s thesis, Instituto Superior Técnico, Universidade Técnica de Lisboa, Portugal.
go back to reference Chana, P. S., & Desai, S. B. (1992). Design of shear reinforments against punching. The Structural Engineer, 70(5), 159–164. Chana, P. S., & Desai, S. B. (1992). Design of shear reinforments against punching. The Structural Engineer, 70(5), 159–164.
go back to reference Dam, T. X., & Wight, J. K. (2015). Flexurally-triggered punching shear failure of reinforced concrete slab-column connections reinforced with headed shear studs arranged in orthogonal and radial layout. Engineering Structures, 110, 258–268.CrossRef Dam, T. X., & Wight, J. K. (2015). Flexurally-triggered punching shear failure of reinforced concrete slab-column connections reinforced with headed shear studs arranged in orthogonal and radial layout. Engineering Structures, 110, 258–268.CrossRef
go back to reference Dinh, H. H., Montesinos, G. J., & Wight, J. K. (2010). Shear behavior of steel fiber-reinforced concrete beams without stirrups reinforcements. ACI Structural Journal, 107(5), 597–606. Dinh, H. H., Montesinos, G. J., & Wight, J. K. (2010). Shear behavior of steel fiber-reinforced concrete beams without stirrups reinforcements. ACI Structural Journal, 107(5), 597–606.
go back to reference Dovich, L., & Wight, J. K. (1996). Lateral response of older flat slab frames and the economic effect on retrofit. Earthquake Spectra, 12(4), 667–691.CrossRef Dovich, L., & Wight, J. K. (1996). Lateral response of older flat slab frames and the economic effect on retrofit. Earthquake Spectra, 12(4), 667–691.CrossRef
go back to reference Eurocode 8—EC8. (2004). Design provision for earthquake resistance of structures. EN 1998-1-1. Eurocode 8—EC8. (2004). Design provision for earthquake resistance of structures. EN 1998-1-1.
go back to reference Graf, W. P., & Mehrain, M. (1992). Analysis and testing of a flat slab concrete building. In World conference on earthquake engineering, Rotter Dam, ISBN90 54100605. Graf, W. P., & Mehrain, M. (1992). Analysis and testing of a flat slab concrete building. In World conference on earthquake engineering, Rotter Dam, ISBN90 54100605.
go back to reference Hawkins, N. M. (1974). Shear strength of slabs with shear reinforcement. ACI Publication, 42(34), 785–815. Hawkins, N. M. (1974). Shear strength of slabs with shear reinforcement. ACI Publication, 42(34), 785–815.
go back to reference ICC, International Building Code—IBC. (2009). Birmingham, AL: International Code Council. ICC, International Building Code—IBC. (2009). Birmingham, AL: International Code Council.
go back to reference Matzke, E. M., Lequesne, R. D., Parra-Montesinos, G. J., & Shield, C. K. (2015). Behavior of biaxially loaded slab-column connections with shear studs. ACI Structural Journal, 112(3), 335.CrossRef Matzke, E. M., Lequesne, R. D., Parra-Montesinos, G. J., & Shield, C. K. (2015). Behavior of biaxially loaded slab-column connections with shear studs. ACI Structural Journal, 112(3), 335.CrossRef
go back to reference Oliveira, D. R., Melo, G. S., & Regan, P. E. (2000). Punching strengths of flat plates with vertical or inclined stirrups. ACI Structural Journal, 97(3), 485–491. Oliveira, D. R., Melo, G. S., & Regan, P. E. (2000). Punching strengths of flat plates with vertical or inclined stirrups. ACI Structural Journal, 97(3), 485–491.
go back to reference Park, R., & Paulay, T. (1974). Reinforced concrete structures. New York: Wiley. Park, R., & Paulay, T. (1974). Reinforced concrete structures. New York: Wiley.
go back to reference Paulay, T., & Priestley, M. J. N. (1992). Seismic design of reinforced concrete and masonry buildings. New York: Wiley.CrossRef Paulay, T., & Priestley, M. J. N. (1992). Seismic design of reinforced concrete and masonry buildings. New York: Wiley.CrossRef
go back to reference Regan, P. E. (1981). Behavior of reinforced concrete flat slabs. Technical Report 89, Construction Industry Research and Information Association (CIRIA), London. Regan, P. E. (1981). Behavior of reinforced concrete flat slabs. Technical Report 89, Construction Industry Research and Information Association (CIRIA), London.
go back to reference Regan, P. E., & Bræstrup, M. W. (1985). Punching shear in reinforced concrete. Comité Euro-International du Béton, Bulletin d’Information, No. 168. Regan, P. E., & Bræstrup, M. W. (1985). Punching shear in reinforced concrete. Comité Euro-International du Béton, Bulletin d’Information, No. 168.
go back to reference Robertson, I. N., & Johnson, G. P. (2004). Non-ductile slab-column connections subjected to cyclic lateral loading. In 13th World conference on earthquake engineering, Vancouver, BC. Robertson, I. N., & Johnson, G. P. (2004). Non-ductile slab-column connections subjected to cyclic lateral loading. In 13th World conference on earthquake engineering, Vancouver, BC.
go back to reference Ruiz, M. F. & Muttoni, A. (2010). Performance and design of punching shear reinforcing systems. In 3rd fib international congress, Maryland. Ruiz, M. F. & Muttoni, A. (2010). Performance and design of punching shear reinforcing systems. In 3rd fib international congress, Maryland.
Metadata
Title
Alternatives to Enhance Flat Slab Ductility
Authors
Mohamed Husain
Ahmed S. Eisa
Ramy Roshdy
Publication date
28-02-2017
Publisher
Springer Netherlands
Published in
International Journal of Concrete Structures and Materials / Issue 1/2017
Print ISSN: 1976-0485
Electronic ISSN: 2234-1315
DOI
https://doi.org/10.1007/s40069-016-0180-5

Other articles of this Issue 1/2017

International Journal of Concrete Structures and Materials 1/2017 Go to the issue