Skip to main content
Log in

Sprinkler protection of manufactured homes with sloped ceilings using prototype limited water supply sprinklers

  • Published:
Fire Technology Aims and scope Submit manuscript

Abstract

Three full-scale fire tests were conducted in a commercial manufactured home 4.3 m wide by 18.3 m long with 10° sloped ceilings. The purpose of the tests was to determine the performance of limited water supply (LWS) sprinklers under a sloped ceiling and to determine whether the minimum distance allowed between sprinklers could be reduced from 2.4 m to 1.8 m. Six prototype LWS sprinklers were installed at a spacing of 1.8 m by 2.4 m in the living room/kitchen area, which measured 4.0 m by 7.2 m. The ceiling and walls were combustible in all three tests, and the room was ventilated by three open windows. The fuel package for all three tests consisted of a vinyl-covered chair with polyurethane padding, double-layered curtains (100% polyester and 50% cotton/50% polyester), and a wooden end table. In the first test, the fuel package was placed in a corner; in the second test, along the wall under the apex of the ceiling between two sprinklers; and in the third test, along the longitudinal wall between two sprinklers. In all tests, no more than two sprinklers actuated. The flow rate with one and two sprinklers operating was 38 pm and 49 pm, respectively. Flow after the first sprinkler actuation was maintained for 10 minutes when one sprinkler actuated and for 7 minutes 40 seconds when two sprinklers actuated. The total flow in each of the three tests was 380ℓ. In all three tests, the sprinklers prevented the curtains and wall paneling from becoming involved in the fire during sprinkler operation. Tenability based on carbon monoxide concentration and gas temperature at the 1.5 m level was maintained in all three tests.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Similar content being viewed by others

References

  1. Bill, R. G., Jr., Kung, H.-C., Hill, E. E., Jr., Chan, T. S., Brown, W. R., “The Development of a Limited Water Supply Sprinkler for Mobile Homes,”Technical Report J.1.OTIN7.RA, Factory Mutual Research Corporation, Norwood, Mass., April 1992.

    Google Scholar 

  2. Bill, R. G., Jr., and Kung, H-C., “Limited-Water-Supply Sprinklers for Manufactured (Mobile) Homes,”Fire Technology, Volume 29, Number 3 (3rd Quarter 1993), pages 203 to 225.

    Google Scholar 

  3. Kung, H-C., Spaulding, R. D., Hill, E. E., Jr., and Symonds, A. P., “Field Evaluation of Residential Prototype Sprinkler—Los Angeles Fire Test Program,”Technical Report J.I.OEOR3.RA(1), Factory Mutual Research Corporation, Norwood, Mass., February 1982.

    Google Scholar 

  4. “Draft Approval Standard for Residential and Limited Water Supply Automatic Sprinklers,”Class Number 2030, Factory Mutual Research Corporation, Norwood, Mass., January 27, 1993.

  5. Shaw, H.,Log #2, 23, 28, 29, Technical Committee Reports (Proposals), NFPA 13D-F93 TCR, Part III, National Fire Protection Association, Quincy, Mass., 1993, pages 496 to 499.

    Google Scholar 

  6. Bill, R. G., Jr., Kung, H-C., Brown, W. R., Hill, E. E., Jr., “Effects of Cathedral and Beamed Ceiling Construction on Residential Sprinkler Performance,”Technical Report J.I.OM3N5.RA(3), Factory Mutual Research Corporation, Norwood, Mass., February 1988.

    Google Scholar 

  7. NFPA 13D,Standard for the Installation of Automatic Sprinklers in One- and Two-Family Dwellings and Manufactured Homes, National Fire Protection Association, Quincy, Mass., 1994.

    Google Scholar 

Download references

Author information

Authors and Affiliations

Authors

Rights and permissions

Reprints and permissions

About this article

Cite this article

Bill, R.G., Hill, E.E. Sprinkler protection of manufactured homes with sloped ceilings using prototype limited water supply sprinklers. Fire Technol 31, 5–16 (1995). https://doi.org/10.1007/BF01305265

Download citation

  • Issue Date:

  • DOI: https://doi.org/10.1007/BF01305265

Keywords

Navigation