Survey and Statistical Parameters of Office Building Fire LoadChinese Full Text
Zhai Yi(China Academy of Building Research,Beijing 100035,China)
Abstract: The office buildings usually have intensive staff and difficulty in fire evacuation.Six office buildings are selected in Beijing to process the fire load survey,and the fitting calculation of survey data is carried out.It is determined the the office moving fire load density average value is 651.63MJ/m2,standard value is 2057MJ/m2,and office building fire load data do not refuse to obey extreme-Ⅰ distribution.In this paper,the distribution form is given,so fire protection design will be more exactly on the data basis.