Overhead transmission line performance with respect to grounding impedance on alpine terrain

verfasst von: L. Schwalt, S. Pack, J. Plesch

Erschienen in: e+i Elektrotechnik und Informationstechnik | Ausgabe 8/2020

Einloggen

Aktivieren Sie unsere intelligente Suche, um passende Fachinhalte oder Patente zu finden.

search-config
loading …

Abstract

The present paper shows a study case of transient effects of direct and indirect lightning discharges on overhead transmission lines with respect to actual grounding impedances of the transmission line system. The transient measurement data was gathered from two 400 kV double-system overhead lines equipped with an overhead ground wire. Additionally installed RC dividers are used to perform transient voltage measurements with high accuracy in amplitude and frequency. The pairing of electric, time and geographic parameters of the used datasets provides the basis for an analysis of the performance of the overhead lines and the high-voltage system influenced by lightning discharges. For this case study, a novel approach is presented where the actual tower-footing grounding impedance of the two systems is related to the transient effects of direct and indirect lightning discharges on the lines as new parameter. The topic, whether it be exposed overhead transmission line systems in the alpine area or line sections with high grounding impedances that show a higher probability of power system faults, is analysed and interpreted in this case study.
The results show no correlation between tower exposure (mountainous or flat terrain) and lightning discharge frequency. For the correlation of the tower footing grounding impedance with the recorded transient measurements, no accumulation of transient effects at towers with higher grounding impedance can be observed either. Regarding the analysed dataset, a high reliability of supply can be expected for systems with a similar setup and comparable lightning parameters. Grounding concepts of existing overhead lines can be validated by these results.

Sie haben noch keine Lizenz? Dann Informieren Sie sich jetzt über unsere Produkte:

Springer Professional "Wirtschaft+Technik"

Online-Abonnement

Mit Springer Professional "Wirtschaft+Technik" erhalten Sie Zugriff auf:

  • über 102.000 Bücher
  • über 537 Zeitschriften

aus folgenden Fachgebieten:

  • Automobil + Motoren
  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Elektrotechnik + Elektronik
  • Energie + Nachhaltigkeit
  • Finance + Banking
  • Management + Führung
  • Marketing + Vertrieb
  • Maschinenbau + Werkstoffe
  • Versicherung + Risiko

Jetzt Wissensvorsprung sichern!

Springer Professional "Technik"

Online-Abonnement

Mit Springer Professional "Technik" erhalten Sie Zugriff auf:

  • über 67.000 Bücher
  • über 390 Zeitschriften

aus folgenden Fachgebieten:

  • Automobil + Motoren
  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Elektrotechnik + Elektronik
  • Energie + Nachhaltigkeit
  • Maschinenbau + Werkstoffe




 

Jetzt Wissensvorsprung sichern!

Springer Professional "Wirtschaft"

Online-Abonnement

Mit Springer Professional "Wirtschaft" erhalten Sie Zugriff auf:

  • über 67.000 Bücher
  • über 340 Zeitschriften

aus folgenden Fachgebieten:

  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Finance + Banking
  • Management + Führung
  • Marketing + Vertrieb
  • Versicherung + Risiko




Jetzt Wissensvorsprung sichern!

Literatur
1.
Zurück zum Zitat Working Group 01 (Lightning) of Study Committee 33 (1991): CIGRE guide to procedures for estimating the lightning performance of transmission lines. Technical brochure (Vol. 63), Paris: CIGRE. Working Group 01 (Lightning) of Study Committee 33 (1991): CIGRE guide to procedures for estimating the lightning performance of transmission lines. Technical brochure (Vol. 63), Paris: CIGRE.
2.
Zurück zum Zitat Poelman, D. R., Schulz, W., Diendorfer, G., Bernardi, M. (2016): The European lightning location system EUCLID – Part 2: Observations. Nat. Hazards Earth Syst. Sci., 16(2), 607. CrossRef Poelman, D. R., Schulz, W., Diendorfer, G., Bernardi, M. (2016): The European lightning location system EUCLID – Part 2: Observations. Nat. Hazards Earth Syst. Sci., 16(2), 607. CrossRef
3.
Zurück zum Zitat Schwalt, L., Plesch, J., Pack, S., Schulz, W., Achleitner, G. (2017): Transient measurements in the Austrian high volt-age transmission system. In International symposium on lightning protection (XIV SIPDA), Natal. Schwalt, L., Plesch, J., Pack, S., Schulz, W., Achleitner, G. (2017): Transient measurements in the Austrian high volt-age transmission system. In International symposium on lightning protection (XIV SIPDA), Natal.
4.
Zurück zum Zitat Plesch, J., Sperling, E., Achleitner, G., Pack, S. (2015): Measurement of transient voltage in a substation. In CIGRE symposium across borders – HVDC systems and market integration, Lund, Report 255. Plesch, J., Sperling, E., Achleitner, G., Pack, S. (2015): Measurement of transient voltage in a substation. In CIGRE symposium across borders – HVDC systems and market integration, Lund, Report 255.
5.
Zurück zum Zitat Plesch, J., Pack, S. (2013): On-site measurement of switching transients in high voltage systems. In 11 Höfler’s days, Portoroz. Plesch, J., Pack, S. (2013): On-site measurement of switching transients in high voltage systems. In 11 Höfler’s days, Portoroz.
6.
Zurück zum Zitat EN/IEC, 62305-3, 2012-12-09 (2012): Protection against lightning - Part 3: Physical damage to structures and life hazard. EN/IEC, 62305-3, 2012-12-09 (2012): Protection against lightning - Part 3: Physical damage to structures and life hazard.
7.
Zurück zum Zitat Diendorfer, G., Pichler, H., Achleitner, G., Broneder, M. (2014): Lightning caused outages in the Austrian Power Grid transmission line network. In International conference of lightning protection (ICLP), 2014 (pp. 152–156). New York: IEEE Press. CrossRef Diendorfer, G., Pichler, H., Achleitner, G., Broneder, M. (2014): Lightning caused outages in the Austrian Power Grid transmission line network. In International conference of lightning protection (ICLP), 2014 (pp. 152–156). New York: IEEE Press. CrossRef
8.
Zurück zum Zitat Schulz, W., Diendorfer, G., Pedeboy, S., Poelman, D. R. (2016): The European lightning location system EUCLID – Part 1: Performance analysis and validation. Nat. Hazards Earth Syst. Sci., 16(2), 595–605. CrossRef Schulz, W., Diendorfer, G., Pedeboy, S., Poelman, D. R. (2016): The European lightning location system EUCLID – Part 1: Performance analysis and validation. Nat. Hazards Earth Syst. Sci., 16(2), 595–605. CrossRef
9.
Zurück zum Zitat Schwalt, L., Pack, S., Schulz, W. (2018): LiOn ground truth data in correlation with ALDIS LLS detections. In International conference of lightning protection (ICLP), Rzeszow. Schwalt, L., Pack, S., Schulz, W. (2018): LiOn ground truth data in correlation with ALDIS LLS detections. In International conference of lightning protection (ICLP), Rzeszow.
10.
Zurück zum Zitat Schulz, W., Vergeiner, C., Pichler, H., Diendorfer, G., Pack, S. (2012): Validation of the Austrian lightning location system ALDIS for negative flashes. In CIGRE C4 colloquium, Sarajevo. Schulz, W., Vergeiner, C., Pichler, H., Diendorfer, G., Pack, S. (2012): Validation of the Austrian lightning location system ALDIS for negative flashes. In CIGRE C4 colloquium, Sarajevo.
11.
Zurück zum Zitat Diendorfer, G., Pichler, H., Schulz, W. (2014): EUCLID located strokes to the Gaisberg tower – accuracy of location and its assigned confidence ellipse. In International lightning detection conference ILDC, Tucson. Diendorfer, G., Pichler, H., Schulz, W. (2014): EUCLID located strokes to the Gaisberg tower – accuracy of location and its assigned confidence ellipse. In International lightning detection conference ILDC, Tucson.
12.
Zurück zum Zitat Diendorfer, G., Schulz, W. (2003): Ground flash density and lightning exposure of power transmission lines. In Power tech conference proceedings. New York: IEEE Press. Diendorfer, G., Schulz, W. (2003): Ground flash density and lightning exposure of power transmission lines. In Power tech conference proceedings. New York: IEEE Press.
13.
Zurück zum Zitat Schulz, W., Cummins, K., Diendorfer, G., Dorninger, M. (2005): Cloud-to-ground lightning in Austria: a 10-year study using data from a lightning location system. J. Geophys. Res., Atmos., 110(D9), D09101. CrossRef Schulz, W., Cummins, K., Diendorfer, G., Dorninger, M. (2005): Cloud-to-ground lightning in Austria: a 10-year study using data from a lightning location system. J. Geophys. Res., Atmos., 110(D9), D09101. CrossRef
14.
Zurück zum Zitat CIGRE Study Committee B2 (2014): Overhead lines. CIGRE green books. CIGRE Study Committee B2 (2014): Overhead lines. CIGRE green books.
Metadaten
Titel
Overhead transmission line performance with respect to grounding impedance on alpine terrain
verfasst von
L. Schwalt
S. Pack
J. Plesch
Publikationsdatum
09.11.2020
Verlag
Springer Vienna
Erschienen in
e+i Elektrotechnik und Informationstechnik / Ausgabe 8/2020
Print ISSN: 0932-383X
Elektronische ISSN: 1613-7620
DOI
https://doi.org/10.1007/s00502-020-00850-5

Weitere Artikel der Ausgabe 8/2020

e & i Elektrotechnik und Informationstechnik 8/2020 Zur Ausgabe

Vorwort

CIGRE 2020

Neuer Inhalt