The Use of Positive Pressure Ventilation Fans During Firefighting Operations in Underground Stations: An Experimental Study

verfasst von: K. Lambert, S. Welch, B. Merci

Erschienen in: Fire Technology | Ausgabe 3/2018

Einloggen

Aktivieren Sie unsere intelligente Suche, um passende Fachinhalte oder Patente zu finden.

search-config
loading …

Abstract

Positive pressure ventilation (PPV) fans are widely used by the fire service during firefighting operations in buildings. Fans are positioned to create a flow through the enclosure. This flow can remove the smoke after the fire or affect the direction of the smoke to support firefighting operations. In subway stations, it is less common to use PPV fans. Here, 106 full-scale tests with up to four fans have been performed in a training building that represents a subway station. The fans were used as extraction fans. The generated flow through the subway station has been measured. The critical velocity for a hypothetical tunnel (W × H: 3.17 × 4.15 m) attached to the subway station has been calculated as 2.37 m/s. Reaching the critical velocity has been used as criterion for ‘success’. All combinations with four fans exceed this velocity, supporting the idea that the fans could be used to facilitate a firefighting operation. The location of the fans was varied. Combinations with three fans on the platform and one at the top of the staircase performed better than combinations with two fans on the platform, one on the landing and one at the top of the staircase. There is an optimum value for the distance between the fans on the platform and the first step of the staircase. This value depends on the angle of inclination of the fans. The fans were not capable of creating a flow that exceeded the critical velocity in the station itself (L × W × H: 60 × 7.15 × 4.53 m). However, a velocity of 2.40 m/s corresponds to a flow rate that will limit the backlayering distance in the station to 15 m. This was only achieved by tests with four fans (three on the platform and one at the top of the staircase).

Sie haben noch keine Lizenz? Dann Informieren Sie sich jetzt über unsere Produkte:

Springer Professional "Technik"

Online-Abonnement

Mit Springer Professional "Technik" erhalten Sie Zugriff auf:

  • über 67.000 Bücher
  • über 390 Zeitschriften

aus folgenden Fachgebieten:

  • Automobil + Motoren
  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Elektrotechnik + Elektronik
  • Energie + Nachhaltigkeit
  • Maschinenbau + Werkstoffe




 

Jetzt Wissensvorsprung sichern!

Springer Professional "Wirtschaft+Technik"

Online-Abonnement

Mit Springer Professional "Wirtschaft+Technik" erhalten Sie Zugriff auf:

  • über 102.000 Bücher
  • über 537 Zeitschriften

aus folgenden Fachgebieten:

  • Automobil + Motoren
  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Elektrotechnik + Elektronik
  • Energie + Nachhaltigkeit
  • Finance + Banking
  • Management + Führung
  • Marketing + Vertrieb
  • Maschinenbau + Werkstoffe
  • Versicherung + Risiko

Jetzt Wissensvorsprung sichern!

Literatur
1.
Zurück zum Zitat Svensson S (2000) Fire ventilation. Swedish Rescue Services Agency, Karlstad Svensson S (2000) Fire ventilation. Swedish Rescue Services Agency, Karlstad
2.
Zurück zum Zitat Ziesler PS, Gunnerson FS, Williams SK (1994) Advances in positive pressure ventilation: live fire tests and laboratory simulation. Fire Technol 30:269–277CrossRef Ziesler PS, Gunnerson FS, Williams SK (1994) Advances in positive pressure ventilation: live fire tests and laboratory simulation. Fire Technol 30:269–277CrossRef
3.
Zurück zum Zitat Vaari J, Hietaniemi J (2000) Smoke ventilation in operational fire fighting. Part 2: multi-story buildings. VTT Publications 419, Technical Research Centre of Finland Vaari J, Hietaniemi J (2000) Smoke ventilation in operational fire fighting. Part 2: multi-story buildings. VTT Publications 419, Technical Research Centre of Finland
4.
Zurück zum Zitat Svensson S (2001) Experimental study of fire ventilation during fire fighting operations. Fire Technol 37:69–85CrossRef Svensson S (2001) Experimental study of fire ventilation during fire fighting operations. Fire Technol 37:69–85CrossRef
5.
Zurück zum Zitat Le Corré F (2001) Ventilation dans les incendies appliqué au métro Parisien, ENSAM, Paris Le Corré F (2001) Ventilation dans les incendies appliqué au métro Parisien, ENSAM, Paris
6.
Zurück zum Zitat Lougheed GD, McBride PJ, Carpenter DW (2002) Positive pressure ventilation for high-rise buildings. National Research Council Canada, Ottawa Lougheed GD, McBride PJ, Carpenter DW (2002) Positive pressure ventilation for high-rise buildings. National Research Council Canada, Ottawa
7.
Zurück zum Zitat Ezekoye OA, Hal CH, Nicks R (2003) Positive pressure ventilation attack for heat transport in a house fire. In: The 6th ASME-JSME thermal engineering joint conference, 16–20 March Ezekoye OA, Hal CH, Nicks R (2003) Positive pressure ventilation attack for heat transport in a house fire. In: The 6th ASME-JSME thermal engineering joint conference, 16–20 March
8.
Zurück zum Zitat Ezekoye OA et al. (2005) Effects of PPV attack on thermal conditions in a compartment downstream of a fire. Fire Technol 41:193–208CrossRef Ezekoye OA et al. (2005) Effects of PPV attack on thermal conditions in a compartment downstream of a fire. Fire Technol 41:193–208CrossRef
9.
Zurück zum Zitat Kerber S, Walton W (2005) Effect of positive pressure ventilation on a room fire, NISTIR 7213. National Institute of Standards and Technology, GaithersburgCrossRef Kerber S, Walton W (2005) Effect of positive pressure ventilation on a room fire, NISTIR 7213. National Institute of Standards and Technology, GaithersburgCrossRef
10.
Zurück zum Zitat Ezekoye OA, Svensson S, Nicks R (2007) Investigating positive pressure ventilation. In: Proceedings of 11th international fire science & engineering conference (Interflam’07), Interscience communications, London, 3–5 September Ezekoye OA, Svensson S, Nicks R (2007) Investigating positive pressure ventilation. In: Proceedings of 11th international fire science & engineering conference (Interflam’07), Interscience communications, London, 3–5 September
11.
Zurück zum Zitat Lambert K, Merci B (2014) Experimental study on the use of positive pressure ventilation for fire service interventions in buildings with staircases. Fire Technol 50:1517–1534CrossRef Lambert K, Merci B (2014) Experimental study on the use of positive pressure ventilation for fire service interventions in buildings with staircases. Fire Technol 50:1517–1534CrossRef
12.
Zurück zum Zitat McCaffrey BJ, Heskestad G (1976) A robust bidirectional low-velocity probe for flame and fire application. Combust Flame 26(1):125–127CrossRef McCaffrey BJ, Heskestad G (1976) A robust bidirectional low-velocity probe for flame and fire application. Combust Flame 26(1):125–127CrossRef
14.
Zurück zum Zitat Oka Y, Atkinson G (1995) Control of smoke flow in tunnel fires. Fire Saf J 25:305–322CrossRef Oka Y, Atkinson G (1995) Control of smoke flow in tunnel fires. Fire Saf J 25:305–322CrossRef
15.
Zurück zum Zitat Wu Y, Bakar M (2000) Control of smoke flow in tunnel fires using longitudinal ventilation systems—a study of the critical velocity. Fire Saf J 35:363–390CrossRef Wu Y, Bakar M (2000) Control of smoke flow in tunnel fires using longitudinal ventilation systems—a study of the critical velocity. Fire Saf J 35:363–390CrossRef
16.
Zurück zum Zitat Fathi T (2010) New perspectives on the critical velocity for smoke control. In: Proceedings: 4th international symposium on tunnel safety and security, Frankfurt am Main, Germany Fathi T (2010) New perspectives on the critical velocity for smoke control. In: Proceedings: 4th international symposium on tunnel safety and security, Frankfurt am Main, Germany
17.
Zurück zum Zitat Li Y (2010) Study of critical velocity and backlayering length in longitudinally ventilated tunnel fires. Fire Saf J 45:361–370CrossRef Li Y (2010) Study of critical velocity and backlayering length in longitudinally ventilated tunnel fires. Fire Saf J 45:361–370CrossRef
18.
Zurück zum Zitat NBN S21-208-2 (2010) Fire protection in buildings—design and calculation of smoke and heat extraction installations—part 2: covered car park buildings NBN S21-208-2 (2010) Fire protection in buildings—design and calculation of smoke and heat extraction installations—part 2: covered car park buildings
19.
Zurück zum Zitat NFPA 130 (2010) Standard for fixed guideway transit and passenger rail systems NFPA 130 (2010) Standard for fixed guideway transit and passenger rail systems
20.
Zurück zum Zitat Bartlett N (2012) Optimization of smoke control systems in underground subway stations. IMFSE dissertation, Ghent University Bartlett N (2012) Optimization of smoke control systems in underground subway stations. IMFSE dissertation, Ghent University
21.
Zurück zum Zitat Lambert K (2014) Positive pressure ventilation in underground systems—an experimental and modelling study. IMFSE dissertation, School of Engineering, The University of Edinburgh Lambert K (2014) Positive pressure ventilation in underground systems—an experimental and modelling study. IMFSE dissertation, School of Engineering, The University of Edinburgh
22.
Zurück zum Zitat Willi J, Madrzykowski D, Weinschenk C (2016) NIST technical note 1938: impact of hose streams on air flows inside a structure Willi J, Madrzykowski D, Weinschenk C (2016) NIST technical note 1938: impact of hose streams on air flows inside a structure
23.
Zurück zum Zitat Bryant RA (2009) A comparison of gas velocity measurements in a full-scale enclosure fire. Fire Saf J 44:793–800CrossRef Bryant RA (2009) A comparison of gas velocity measurements in a full-scale enclosure fire. Fire Saf J 44:793–800CrossRef
Metadaten
Titel
The Use of Positive Pressure Ventilation Fans During Firefighting Operations in Underground Stations: An Experimental Study
verfasst von
K. Lambert
S. Welch
B. Merci
Publikationsdatum
17.01.2018
Verlag
Springer US
Erschienen in
Fire Technology / Ausgabe 3/2018
Print ISSN: 0015-2684
Elektronische ISSN: 1572-8099
DOI
https://doi.org/10.1007/s10694-018-0700-8

Weitere Artikel der Ausgabe 3/2018

Fire Technology 3/2018 Zur Ausgabe