Verification of withstand capability for very fast transients of a 200 MVA, 500 kV GSU transformer by modelling and testing

verfasst von: A. Rabel, J.-J. Zhou

Erschienen in: e+i Elektrotechnik und Informationstechnik | Ausgabe 8/2020

Einloggen

Aktivieren Sie unsere intelligente Suche, um passende Fachinhalte oder Patente zu finden.

search-config
loading …

Abstract

Transformers in the network are often exposed to voltage stresses that are different from the impulses during the factory assessment tests (FAT). In many cases transformers can withstand these voltages. In combination with gas-insulated switch gears (GIS), it is typical that these voltages are characterized by a very high steepness in combination with a short duration time called very fast transients (VFT). Since for VFT voltages the difference to the FAT is remarkable, customers ask for an extended proof of the withstand capability.
It is also clear that customers are conducting their own system studies, on the one hand, to get more detailed knowledge about voltage stresses to be expected at switching events and fault events. On the other hand, it is important to consider these results when doing the specification for transformers to connect to GIS.
To cover these requirements, a step-by-step approach was followed starting with providing simplified transformer models and calculating the frequency response based on the manufacturer’s white-box model. These models are delivered to the customer. Resonance frequencies are derived, and the safety margins as well a proof for acceptable resonant voltages, e.g., the HV terminal, is given.
Next, to prove the withstand capability for voltage stresses at energisation, inductive opening, reignitions and disconnecting events are performed. Due to the content of very high frequencies in the signals – going up to 5 MHz – it is necessary to use proper models during the design process of the transformer. Turn-wise models of the transformer windings provide a sufficient resolution for the required frequency range (>10 MHz). The use of turn-wise models of the transformer’s windings is mandatory.
It is a challenge that a transformer can reliably withstand the VFT voltages. The withstand capability is proven by numerical simulation as well as by a special test. In the test sequence a very steep chopping, by applying a special SF6 chopping device with customer-specified voltage levels, finally successfully proved the transformer’s withstand capability for VFT.

Sie haben noch keine Lizenz? Dann Informieren Sie sich jetzt über unsere Produkte:

Springer Professional "Wirtschaft+Technik"

Online-Abonnement

Mit Springer Professional "Wirtschaft+Technik" erhalten Sie Zugriff auf:

  • über 102.000 Bücher
  • über 537 Zeitschriften

aus folgenden Fachgebieten:

  • Automobil + Motoren
  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Elektrotechnik + Elektronik
  • Energie + Nachhaltigkeit
  • Finance + Banking
  • Management + Führung
  • Marketing + Vertrieb
  • Maschinenbau + Werkstoffe
  • Versicherung + Risiko

Jetzt Wissensvorsprung sichern!

Springer Professional "Technik"

Online-Abonnement

Mit Springer Professional "Technik" erhalten Sie Zugriff auf:

  • über 67.000 Bücher
  • über 390 Zeitschriften

aus folgenden Fachgebieten:

  • Automobil + Motoren
  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Elektrotechnik + Elektronik
  • Energie + Nachhaltigkeit
  • Maschinenbau + Werkstoffe




 

Jetzt Wissensvorsprung sichern!

Springer Professional "Wirtschaft"

Online-Abonnement

Mit Springer Professional "Wirtschaft" erhalten Sie Zugriff auf:

  • über 67.000 Bücher
  • über 340 Zeitschriften

aus folgenden Fachgebieten:

  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Finance + Banking
  • Management + Führung
  • Marketing + Vertrieb
  • Versicherung + Risiko




Jetzt Wissensvorsprung sichern!

Literatur
1.
Zurück zum Zitat CIGRE TB 577A (2014): Electrical transient interaction between transformers and the power system, part 1- expertise, joint working group A2/C4.39. CIGRE TB 577A (2014): Electrical transient interaction between transformers and the power system, part 1- expertise, joint working group A2/C4.39.
2.
Zurück zum Zitat CIGRE TB 577B (2014): Electrical transient interaction between transformers and the power system, part 2- case studies, joint working group A2/C4.39. CIGRE TB 577B (2014): Electrical transient interaction between transformers and the power system, part 2- case studies, joint working group A2/C4.39.
3.
Zurück zum Zitat Narimatsu, S., Yamaguchi, K., Nakano, S., Maruyama, S. (1981): Interrupting performance of capacitive current by disconnecting switch for gas insulated switchgear. IEEE Trans. Power Appar. Syst., PAS-100(6), 2726–2732. CrossRef Narimatsu, S., Yamaguchi, K., Nakano, S., Maruyama, S. (1981): Interrupting performance of capacitive current by disconnecting switch for gas insulated switchgear. IEEE Trans. Power Appar. Syst., PAS-100(6), 2726–2732. CrossRef
4.
Zurück zum Zitat Boeck, W., Witzmann, R. (1989): Critical GIS configurations with respect to VFT. In Sixth international symposium on high voltage engineering, New Orleans, LA, USA, August 28–September 1, 1989. Boeck, W., Witzmann, R. (1989): Critical GIS configurations with respect to VFT. In Sixth international symposium on high voltage engineering, New Orleans, LA, USA, August 28–September 1, 1989.
5.
Zurück zum Zitat Ikeda, M., Fukumoto, S., Takao, H., Ohtsuka, S., Haginomori, E., Hikita, M. (2002): Breakdown characteristics of oil and paper insulation for a very fast transient voltage. Electr. Eng. Jpn., 141(4), 16–24. CrossRef Ikeda, M., Fukumoto, S., Takao, H., Ohtsuka, S., Haginomori, E., Hikita, M. (2002): Breakdown characteristics of oil and paper insulation for a very fast transient voltage. Electr. Eng. Jpn., 141(4), 16–24. CrossRef
6.
Zurück zum Zitat Nakanishi, K., Fujita, S., Kurita, H., Kishi, A., Shibuya, Y. (1997): High frequency voltage oscillation in transformer windings and electrical breakdown properties of interturn insulation immersed in oil at VFT voltage. In IEEE annual report-conference on electrical insulation and dielectric phenomena, Minneapolis, October 19-22, 1997. Nakanishi, K., Fujita, S., Kurita, H., Kishi, A., Shibuya, Y. (1997): High frequency voltage oscillation in transformer windings and electrical breakdown properties of interturn insulation immersed in oil at VFT voltage. In IEEE annual report-conference on electrical insulation and dielectric phenomena, Minneapolis, October 19-22, 1997.
9.
Zurück zum Zitat Wang, M. (1991): The electrical breakdown characteristics of oil/paper insulation under fast front voltages. Master-thesis, University of British Columbia. Wang, M. (1991): The electrical breakdown characteristics of oil/paper insulation under fast front voltages. Master-thesis, University of British Columbia.
Metadaten
Titel
Verification of withstand capability for very fast transients of a 200 MVA, 500 kV GSU transformer by modelling and testing
verfasst von
A. Rabel
J.-J. Zhou
Publikationsdatum
13.11.2020
Verlag
Springer Vienna
Erschienen in
e+i Elektrotechnik und Informationstechnik / Ausgabe 8/2020
Print ISSN: 0932-383X
Elektronische ISSN: 1613-7620
DOI
https://doi.org/10.1007/s00502-020-00849-y

Weitere Artikel der Ausgabe 8/2020

e & i Elektrotechnik und Informationstechnik 8/2020 Zur Ausgabe

Neuer Inhalt