Review on Performance Metrics for Energy Efficiency in Data Center: The Role of Thermal Management

verfasst von : Alfonso Capozzoli, Marta Chinnici, Marco Perino, Gianluca Serale

Erschienen in: Energy Efficient Data Centers

Verlag: Springer International Publishing

Aktivieren Sie unsere intelligente Suche, um passende Fachinhalte oder Patente zu finden.

search-config
loading …

Abstract

Energy consumption and thermal performance are the two most important tasks in data centers (DCs) facility management. In recent years, to monitor and control their variation several performance metrics were introduced. In this paper an overview on the main important energy and thermal metrics is provided. A critical analysis to investigate mutual relations among metrics was performed, with the aim to clarify some physical aspects regarding the assessment of DC global energy performance.
Indeed, although these metrics are commonly used to assess the energy efficiency of DCs, their usefulness for encouraging lower energy consumption was poorly investigated. Moreover, an analysis on the effect of the DC thermal performance on metrics was done. The thermal management assume a key role for achieving energy saving during the operation of a DC and for the improvement of the IT equipment reliability.

Sie haben noch keine Lizenz? Dann Informieren Sie sich jetzt über unsere Produkte:

Springer Professional "Wirtschaft+Technik"

Online-Abonnement

Mit Springer Professional "Wirtschaft+Technik" erhalten Sie Zugriff auf:

  • über 102.000 Bücher
  • über 537 Zeitschriften

aus folgenden Fachgebieten:

  • Automobil + Motoren
  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Elektrotechnik + Elektronik
  • Energie + Nachhaltigkeit
  • Finance + Banking
  • Management + Führung
  • Marketing + Vertrieb
  • Maschinenbau + Werkstoffe
  • Versicherung + Risiko

Jetzt Wissensvorsprung sichern!

Springer Professional "Technik"

Online-Abonnement

Mit Springer Professional "Technik" erhalten Sie Zugriff auf:

  • über 67.000 Bücher
  • über 390 Zeitschriften

aus folgenden Fachgebieten:

  • Automobil + Motoren
  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Elektrotechnik + Elektronik
  • Energie + Nachhaltigkeit
  • Maschinenbau + Werkstoffe




 

Jetzt Wissensvorsprung sichern!

Springer Professional "Wirtschaft"

Online-Abonnement

Mit Springer Professional "Wirtschaft" erhalten Sie Zugriff auf:

  • über 67.000 Bücher
  • über 340 Zeitschriften

aus folgenden Fachgebieten:

  • Bauwesen + Immobilien
  • Business IT + Informatik
  • Finance + Banking
  • Management + Führung
  • Marketing + Vertrieb
  • Versicherung + Risiko




Jetzt Wissensvorsprung sichern!

Literatur
1.
Zurück zum Zitat ASHRAE: 2011 Thermal Guidelines for Data Processing Environments – Expanded Data Center Classes and Usage Guidance. Technical report, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (2011) ASHRAE: 2011 Thermal Guidelines for Data Processing Environments – Expanded Data Center Classes and Usage Guidance. Technical report, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (2011)
2.
Zurück zum Zitat The Green Grid: The Green Grid Energy Policy Research for Data Centres. Technical report, White Paper #25, The Green Grid (2009) The Green Grid: The Green Grid Energy Policy Research for Data Centres. Technical report, White Paper #25, The Green Grid (2009)
3.
Zurück zum Zitat Tozer, R., Flucker, S., Romano, A.: Scalable data centre efficiency. In: CIBSE Technical Symposium, Liverpool John Moores University, Liverpool, UK, 11–12 April 2013 Tozer, R., Flucker, S., Romano, A.: Scalable data centre efficiency. In: CIBSE Technical Symposium, Liverpool John Moores University, Liverpool, UK, 11–12 April 2013
4.
Zurück zum Zitat Barroso, L.A., Hölzle, U.: The datacenter as a computer: an introduction to the design of warehouse-scale machines. Synth. Lect. Comput. Archit. 4(1), 1–108 (2009)CrossRef Barroso, L.A., Hölzle, U.: The datacenter as a computer: an introduction to the design of warehouse-scale machines. Synth. Lect. Comput. Archit. 4(1), 1–108 (2009)CrossRef
5.
Zurück zum Zitat Koomey, J.G.: Worldwide electricity used in data centers. Environ. Res. Lett. 3(3), 034008 (2008)CrossRef Koomey, J.G.: Worldwide electricity used in data centers. Environ. Res. Lett. 3(3), 034008 (2008)CrossRef
6.
Zurück zum Zitat Schaeppi, B., Bogner, T., Schloesser, A., Stobbe, L., De Asuncao, M.D.: Metrics for energy efficiency assessment in data centers and server rooms. In: Electronics Goes Green 2012+ (EGG), pp. 1–6. IEEE (2012) Schaeppi, B., Bogner, T., Schloesser, A., Stobbe, L., De Asuncao, M.D.: Metrics for energy efficiency assessment in data centers and server rooms. In: Electronics Goes Green 2012+ (EGG), pp. 1–6. IEEE (2012)
7.
Zurück zum Zitat The uptime institute: heat density trends in data processing, computer systems and telecommunication equipment. Technical report, The Uptime Institute (2000) The uptime institute: heat density trends in data processing, computer systems and telecommunication equipment. Technical report, The Uptime Institute (2000)
9.
Zurück zum Zitat Flucker, S., Tozer, R.: Data centre energy efficiency analysis to minimize total cost of ownership. Building Serv. Eng. Res. Technol. 34(1), 103–117 (2013)CrossRef Flucker, S., Tozer, R.: Data centre energy efficiency analysis to minimize total cost of ownership. Building Serv. Eng. Res. Technol. 34(1), 103–117 (2013)CrossRef
10.
Zurück zum Zitat The Green Grid: Water Usage Effectiveness (WUE): A Green Grid Data Center Sustainability Metric. Technical report, White Paper #35, The Green Grid (2011) The Green Grid: Water Usage Effectiveness (WUE): A Green Grid Data Center Sustainability Metric. Technical report, White Paper #35, The Green Grid (2011)
11.
Zurück zum Zitat The Green Grid: Carbon Usage Effectiveness (CUE): A Green Grid Data Center Sustainability Metric. Technical report, White Paper #32, The Green Grid (2010) The Green Grid: Carbon Usage Effectiveness (CUE): A Green Grid Data Center Sustainability Metric. Technical report, White Paper #32, The Green Grid (2010)
13.
Zurück zum Zitat Sullivan, R.F.: Reducing bypass airflow is essential for eliminating computer room hot spots. Technical report, The Uptime Institute (2004) Sullivan, R.F.: Reducing bypass airflow is essential for eliminating computer room hot spots. Technical report, The Uptime Institute (2004)
14.
Zurück zum Zitat Cho, J., Kim, B.S.: Evaluation of air management system’s thermal performance for superior cooling efficiency in high-density data centers. Energy Build. 43(9), 2145–2155 (2011)CrossRef Cho, J., Kim, B.S.: Evaluation of air management system’s thermal performance for superior cooling efficiency in high-density data centers. Energy Build. 43(9), 2145–2155 (2011)CrossRef
15.
Zurück zum Zitat Sharma, R.K., Bash, C.E., Patel, C.D.: Dimensionless parameters for evaluation of thermal design and performance of large-scale data centers. In: 8th ASME/AIAA Joint Thermophysics and Heat Transfer Conference, pp. 1–1 (2002) Sharma, R.K., Bash, C.E., Patel, C.D.: Dimensionless parameters for evaluation of thermal design and performance of large-scale data centers. In: 8th ASME/AIAA Joint Thermophysics and Heat Transfer Conference, pp. 1–1 (2002)
16.
Zurück zum Zitat Tang, Q., Mukherjee, T., Gupta, S.K., Cayton, P.: Sensor-based fast thermal evaluation model for energy efficient high-performance datacenters. In: Fourth International Conference on Intelligent Sensing and Information Processing, ICISIP 2006, pp. 203–208. IEEE (2006) Tang, Q., Mukherjee, T., Gupta, S.K., Cayton, P.: Sensor-based fast thermal evaluation model for energy efficient high-performance datacenters. In: Fourth International Conference on Intelligent Sensing and Information Processing, ICISIP 2006, pp. 203–208. IEEE (2006)
17.
Zurück zum Zitat Schmidt, R.R., Cruz, E.E., Iyengar, M.: Challenges of data center thermal management. IBM J. Res. Dev. 49(4.5), 709–723 (2005)CrossRef Schmidt, R.R., Cruz, E.E., Iyengar, M.: Challenges of data center thermal management. IBM J. Res. Dev. 49(4.5), 709–723 (2005)CrossRef
18.
Zurück zum Zitat Herrlin, M.K.: Rack cooling effectiveness in data centers and telecom central offices: the rack cooling index (RCI). ASHRAE Trans. 111(2), 725–731 (2005) Herrlin, M.K.: Rack cooling effectiveness in data centers and telecom central offices: the rack cooling index (RCI). ASHRAE Trans. 111(2), 725–731 (2005)
19.
Zurück zum Zitat Tozer, R., Kurkjian, C., Salim, M.: Air management metrics in data centers. ASHRAE Trans. 115(1), 63–70 (2009) Tozer, R., Kurkjian, C., Salim, M.: Air management metrics in data centers. ASHRAE Trans. 115(1), 63–70 (2009)
20.
Zurück zum Zitat Herrlin, M.K.: Improved data center energy efficiency and thermal performance by advanced airflow analysis. In: Digital Power Forum, pp. 10–12, San Francisco (2007) Herrlin, M.K.: Improved data center energy efficiency and thermal performance by advanced airflow analysis. In: Digital Power Forum, pp. 10–12, San Francisco (2007)
21.
Zurück zum Zitat Vangilder, J.W., Shrivastava, S.K.: Capture index: an airflow-based rack cooling performance metric. ASHRAE Trans. 113(1), 126–136 (2007) Vangilder, J.W., Shrivastava, S.K.: Capture index: an airflow-based rack cooling performance metric. ASHRAE Trans. 113(1), 126–136 (2007)
22.
Zurück zum Zitat Pelley, S., Meisner, D., Wenisch, T.F., VanGilder, J.W.: Understanding and abstracting total data center power. In: Workshop on Energy-Efficient Design, June 2009 Pelley, S., Meisner, D., Wenisch, T.F., VanGilder, J.W.: Understanding and abstracting total data center power. In: Workshop on Energy-Efficient Design, June 2009
23.
Zurück zum Zitat Chinnici, M., Quintiliani, A.: An example of methodology to assess energy efficiency improvements in datacenters. In: 2013 Third International Conference on Cloud and Green Computing (CGC), pp. 459–463. IEEE, Karlsruhe (2013) Chinnici, M., Quintiliani, A.: An example of methodology to assess energy efficiency improvements in datacenters. In: 2013 Third International Conference on Cloud and Green Computing (CGC), pp. 459–463. IEEE, Karlsruhe (2013)
24.
Zurück zum Zitat Mathew, P., Ganguly, S., Greenberg, S., Sartor, D.: Self-benchmarking guide for data centers: metrics, benchmarks, actions. Technical report, Lawrence Berkeley National Laboratory, Berkeley, California, June 2010 Mathew, P., Ganguly, S., Greenberg, S., Sartor, D.: Self-benchmarking guide for data centers: metrics, benchmarks, actions. Technical report, Lawrence Berkeley National Laboratory, Berkeley, California, June 2010
25.
Zurück zum Zitat Durand-Estebe, B., Le Bot, C., Mancos, J.N., Arquis, E.: Data center optimization using PID regulation in CFD simulations. Energy Build. 66, 154–164 (2013)CrossRef Durand-Estebe, B., Le Bot, C., Mancos, J.N., Arquis, E.: Data center optimization using PID regulation in CFD simulations. Energy Build. 66, 154–164 (2013)CrossRef
26.
Zurück zum Zitat Dumitru, I., Fagarasan, I., Iliescu, S., Said, Y.H., Ploix, S.: Increasing energy efficiency in data centers using energy management. In: 2011 IEEE/ACM International Conference on Green Computing and Communications (GreenCom), pp. 159–165. IEEE (2011) Dumitru, I., Fagarasan, I., Iliescu, S., Said, Y.H., Ploix, S.: Increasing energy efficiency in data centers using energy management. In: 2011 IEEE/ACM International Conference on Green Computing and Communications (GreenCom), pp. 159–165. IEEE (2011)
27.
Zurück zum Zitat Yuventi, J., Mehdizadeh, R.: A critical analysis of power usage effectiveness and its use in communicating data center energy consumption. Energy Build. 64, 90–94 (2013)CrossRef Yuventi, J., Mehdizadeh, R.: A critical analysis of power usage effectiveness and its use in communicating data center energy consumption. Energy Build. 64, 90–94 (2013)CrossRef
28.
Zurück zum Zitat The green grid: the green grid metrics: data center infrastructure efficiency (DCiE) detailed analysis. Technical report, White Paper #14, The Green Grid (2008) The green grid: the green grid metrics: data center infrastructure efficiency (DCiE) detailed analysis. Technical report, White Paper #14, The Green Grid (2008)
29.
Zurück zum Zitat The green grid: the green grid data center efficiency metrics: PUE and DCIE. Technical report, White Paper #6, The Green Grid (2007) The green grid: the green grid data center efficiency metrics: PUE and DCIE. Technical report, White Paper #6, The Green Grid (2007)
30.
Zurück zum Zitat ETSI: Operational Energy Efficiency for User (OEU): Global KPI for Data Centers. Technical report, ETSI (2013) ETSI: Operational Energy Efficiency for User (OEU): Global KPI for Data Centers. Technical report, ETSI (2013)
32.
Zurück zum Zitat Patterson, M.K., Poole, S.W., Hsu, C.-H., Maxwell, D., Tschudi, W., Coles, H., Martinez, D.J., Bates, N.: TUE, a new energy-efficiency metric applied at ORNL’s Jaguar. In: Kunkel, J.M., Ludwig, T., Meuer, H.W. (eds.) ISC 2013. LNCS, vol. 7905, pp. 372–382. Springer, Heidelberg (2013)CrossRef Patterson, M.K., Poole, S.W., Hsu, C.-H., Maxwell, D., Tschudi, W., Coles, H., Martinez, D.J., Bates, N.: TUE, a new energy-efficiency metric applied at ORNL’s Jaguar. In: Kunkel, J.M., Ludwig, T., Meuer, H.W. (eds.) ISC 2013. LNCS, vol. 7905, pp. 372–382. Springer, Heidelberg (2013)CrossRef
33.
Zurück zum Zitat Patterson, M.K.: The effect of data center temperature on energy efficiency. In: 11th Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM 2008. pp. 1167–1174. IEEE (2008) Patterson, M.K.: The effect of data center temperature on energy efficiency. In: 11th Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM 2008. pp. 1167–1174. IEEE (2008)
34.
Zurück zum Zitat The Green Grid: The Green Grid Productivity Indicator. Technical report, White Paper #15, The Green Grid (2008) The Green Grid: The Green Grid Productivity Indicator. Technical report, White Paper #15, The Green Grid (2008)
35.
Zurück zum Zitat The Green Grid: ERE: a Metric for Measuring the Benefit of Reuse Energy from a Data Center. Technical report, White Paper #29, The Green Grid (2010) The Green Grid: ERE: a Metric for Measuring the Benefit of Reuse Energy from a Data Center. Technical report, White Paper #29, The Green Grid (2010)
36.
Zurück zum Zitat Cho, J., Yang, J., Park, W.: Evaluation of air distribution system’s airflow performance for cooling energy savings in high-density data centers. Energy Build. 68, 270–279 (2014)CrossRef Cho, J., Yang, J., Park, W.: Evaluation of air distribution system’s airflow performance for cooling energy savings in high-density data centers. Energy Build. 68, 270–279 (2014)CrossRef
37.
Zurück zum Zitat Tang, Q., Gupta, S.K.S., Varsamopoulos, G.: Thermal-aware task scheduling for data centers through minimizing heat recirculation. In: 2007 IEEE International Conference on Cluster Computing, pp. 129–138, (2007). doi:10.1109/CLUSTR.2007.4629225 Tang, Q., Gupta, S.K.S., Varsamopoulos, G.: Thermal-aware task scheduling for data centers through minimizing heat recirculation. In: 2007 IEEE International Conference on Cluster Computing, pp. 129–138, (2007). doi:10.​1109/​CLUSTR.​2007.​4629225
38.
Zurück zum Zitat Moss, D., Bean, J.H.: Energy impact of increased server inlet temperature. Technical report, APC White Paper, 138 (2009) Moss, D., Bean, J.H.: Energy impact of increased server inlet temperature. Technical report, APC White Paper, 138 (2009)
39.
Zurück zum Zitat Biswas, S., Tiwari, M., Sherwood, T., Theogarajan, L., Chong, F.T.: Fighting fire with fire: modeling the datacenter-scale effects of targeted superlattice thermal management. In: 2011 38th Annual International Symposium on Computer Architecture (ISCA), pp. 331–340. IEEE (2011) Biswas, S., Tiwari, M., Sherwood, T., Theogarajan, L., Chong, F.T.: Fighting fire with fire: modeling the datacenter-scale effects of targeted superlattice thermal management. In: 2011 38th Annual International Symposium on Computer Architecture (ISCA), pp. 331–340. IEEE (2011)
40.
Zurück zum Zitat Favoino, F., Capozzoli, A., Perino, M.: Temperature field real-time diagnosis by means of infrared imaging in data elaboration center. In: Abramowicz, W., Llorente, I.M., Surridge, M., Zisman, A., Vayssière, J. (eds.) Proceedings of the 8th International Symposium on Heating, Ventilation and Air Conditioning. LNEE, vol. 263. Springer, Heidelberg (2014) Favoino, F., Capozzoli, A., Perino, M.: Temperature field real-time diagnosis by means of infrared imaging in data elaboration center. In: Abramowicz, W., Llorente, I.M., Surridge, M., Zisman, A., Vayssière, J. (eds.) Proceedings of the 8th International Symposium on Heating, Ventilation and Air Conditioning. LNEE, vol. 263. Springer, Heidelberg (2014)
41.
42.
Zurück zum Zitat Lu, X., Lu, T., Remes, M., Viljanen, M.: Preliminary analysis of energy efficiency in data center: case study. World Acad. Sci. Eng. Technol. 5(4), 04–26 (2011) Lu, X., Lu, T., Remes, M., Viljanen, M.: Preliminary analysis of energy efficiency in data center: case study. World Acad. Sci. Eng. Technol. 5(4), 04–26 (2011)
43.
Zurück zum Zitat Qian, X., Li, Z., Li, Z.: A thermal environmental analysis method for data centers. Int. J. Heat Mass Transf. 62, 579–585 (2013)CrossRef Qian, X., Li, Z., Li, Z.: A thermal environmental analysis method for data centers. Int. J. Heat Mass Transf. 62, 579–585 (2013)CrossRef
44.
Zurück zum Zitat Guo, Z.Y., Zhu, H.Y., Liang, X.G.: Entransy - a physical quantity describing heat transfer ability. Int. J. Heat Mass Transf. 50(13), 2545–2556 (2007)CrossRefMATH Guo, Z.Y., Zhu, H.Y., Liang, X.G.: Entransy - a physical quantity describing heat transfer ability. Int. J. Heat Mass Transf. 50(13), 2545–2556 (2007)CrossRefMATH
45.
Zurück zum Zitat Sharma, R.K., Bash, C.E., Patel, C.D., Friedrich, R.J., Chase, J.S.: Balance of power: dynamic thermal management for internet data centers. Internet Comput. IEEE 9(1), 42–49 (2005)CrossRef Sharma, R.K., Bash, C.E., Patel, C.D., Friedrich, R.J., Chase, J.S.: Balance of power: dynamic thermal management for internet data centers. Internet Comput. IEEE 9(1), 42–49 (2005)CrossRef
46.
Zurück zum Zitat Moore, J., Chase, J., Ranganathan, P., Sharma, R.: Making scheduling “cool”: temperature aware workload placement in data centers. Technical report, in USENIX Annual Technical Conference (2005) Moore, J., Chase, J., Ranganathan, P., Sharma, R.: Making scheduling “cool”: temperature aware workload placement in data centers. Technical report, in USENIX Annual Technical Conference (2005)
47.
Zurück zum Zitat Mukherjee, T., Banerjee, A., Varsamopoulos, G., Gupta, S.K., Rungta, S.: Spatio-temporal thermal-aware job scheduling to minimize energy consumption in virtualized heterogeneous data centers. Comput. Netw. 53(17), 2888–2904 (2009)CrossRefMATH Mukherjee, T., Banerjee, A., Varsamopoulos, G., Gupta, S.K., Rungta, S.: Spatio-temporal thermal-aware job scheduling to minimize energy consumption in virtualized heterogeneous data centers. Comput. Netw. 53(17), 2888–2904 (2009)CrossRefMATH
Metadaten
Titel
Review on Performance Metrics for Energy Efficiency in Data Center: The Role of Thermal Management
verfasst von
Alfonso Capozzoli
Marta Chinnici
Marco Perino
Gianluca Serale
Copyright-Jahr
2015
DOI
https://doi.org/10.1007/978-3-319-15786-3_9

Premium Partner