Introduction
Methodology
-
Parameter group A: Operational and user errors in PACS
-
Parameter group C: Design parameters and planning foundations for building technology
Case study
Parameter category | Parameter | Value | Unit |
---|---|---|---|
Building physics parameters | U value external wall | 0.35 | W/(m2K) |
U value roof | 0.25 | W/(m2K) | |
U value baseplate | 0.40 | W/(m2K) | |
U value window | 1.10 | W/(m2K) | |
Lighting | 13 | W/m2 | |
120 | lm/W | ||
User parameters | Illuminance level | 500/200/100 | lx |
Internal loads | 100 | W/person | |
Usage time | 5:00–18:00 | o’clock |
Parameter category | Parameter | Value | Unit | References |
---|---|---|---|---|
Controlled values | Minimum room air temperature setpoint | 21 | °C | (DIN, V 18599-10, 2018) |
Maximum room air temperature setpoint | 24 | °C | (DIN, V 18599-10, 2018) | |
Temperature reduction outside of usage time | 4 | K | (DIN, V 18599-10, 2018) | |
Minimum temperature setpoint for exhaust air (protection against icing) | 3 | °C | (Siemens, 2018) | |
Hot water temperatures for heating registers | 70/55 | °C | (DIN, V 18599-7, 2016) | |
Setpoint range for the relative humidity in the zones | 25–60 | % | (DIN, EN 16798-1, 2015) | |
Maximum CO2 content above the outside air concentration | 500 | ppm | (DIN, EN 16798-1, 2015) | |
Installation performance values | Efficiency heat recovery coefficient | 75 | % | (Schramek & Recknagel, 2011) |
Gas boiler efficiency | 89 | % | (Schramek & Recknagel, 2011) | |
EER compression chiller | 3 | - | (Schramek & Recknagel, 2011) |
Name and brief description | Unit | Distribution |
---|---|---|
Error 1.1—volume flow zone level | l/(sm2) | ~ N(1.238; 0.062) |
Error 2.1—differential pressure supply air fan | Pa | ~ N(600.0; 30.0) |
Error 2.2—differential pressure exhaust air fan | Pa | ~ N(500.0; 25.0) |
Error 2.4—start of operation of partial air conditioning system | o’clock | ~ N(05:00; 0.650) |
Error 2.5—termination of partial air conditioning system | o’clock | ~ N(18:00; 0.650) |
Error 3.1—adjustment range of the air recirculation flap | - | ~ N(0.000; 0.053) |
Error 4.1—blocking temperature heat recovery | °C | ~ N(3.000; 0.150) |
Error 4.5—heat number of the heat recovery | - | ~ N(0.750; 0.038) |
Error 5.1—heat transfer pre-heating register | - | ~ N(1.000; 0.050) |
Error 5.2—control valve pre-heating register | kg/s | ~ N(0.000; 0.009) |
Error 5.3—pump pre- and post-heating register | Pa | ~ N(30000.0; 1500.0) |
Error 5.4—temperature spread pre-heating register | °C | ~ N(15.000; 0.750) |
Error 5.6—heat transfer post-heating register | - | ~ N(1.000; 0.050) |
Error 5.7—control valve post-heating register | kg/s | ~ N(0.000; 0.009) |
Error 5.8—temperature spread post-heating register | °C | ~ N(15.000; 0.750) |
Error 5.10—heat transfer cooling register | - | ~ N(1.000; 0.050) |
Error 5.11—control valve cooling register | kg/s | ~ N(0.000; 0.018) |
Error 5.12—pump cooling register | Pa | ~ N(30000.0; 1500.0) |
Error 5.13—temperature spread cooling register | °C | ~ N(6.0; 0.3) |
Error 5.19—exhaust air temperature sensor offset | °C | ~ N(0.000; 1.080) |
Error 6.1—humidity sensor offset | % | ~ N(0.000; 1.701) |
Error 8.1—number of people | - | ~ N(2.0; 0.1) |
Error 8.2—sun protection | W/m2 | ~ N(200.0; 10.0) |
Error 8.3—window opening time | h/day | ~ N(0.000; 0.550) |
Name and brief description (parameter group) | Unit | Distribution | Step 1 | Step 2 | References |
---|---|---|---|---|---|
Error 1.1—volume flow zone level (A) | l/(sm2) | ~ U(0.000; 1.609) | X | - | - |
Error 2.1—differential pressure supply air fan (A) | Pa | ~ U(0.0; 700.0) | X | - | - |
Error 2.5—termination of partial air conditioning system (A) | o’clock | ~ U(05:00; 24:00) | X | X | - |
Error 5.8—temperature spread post-heating register (A) | °C | ~ U(0.1; 50.0) | X | - | - |
Error 5.19—exhaust air temperature sensor offset (A) | °C | ~ N(0.000; 0.970) | X | - | (Brohus & Heiselberg, 2009) |
Error 8.1—number of people (A) | - | ~ N(2.0; 1.0) | X | X | (Macdonald, 2002) |
Error 8.2—sun protection (A) | W/m2 | ~ U(0.0; 1000.0) | X | X | (Kaltschmitt et al., 2013) |
Error 8.3—window opening time (A) | h/day | ~ U(0.0; 0.25) | X | X | (Osterhage, 2018) |
Minimum room air temperature setpoint (B) | °C | ~ N(21.000; 0.970) | - | X | (Brohus & Heiselberg, 2009) |
Maximum room air temperature setpoint (B) | °C | ~ N(24.000; 0.970) | - | X | (Brohus & Heiselberg, 2009) |
Gas boiler efficiency (C) | - | ~ U(0.880; 0.990) | - | X | (Schramek & Recknagel, 2011) |
Plant engineering (start of operation) (C) | o’clock | ~ U(03:00; 05:00) | - | X | (DIN, V 18599-10, 2018) |
Plant engineering (end of operation) (C) | o’clock | ~ U(18:00; 21:00) | - | X | |
Flow temperature cooling register (C) | °C | ~ U(6.0; 14.0) | - | X | (DIN, V 18599-7, 2016) |